Dial type thermometers are designed to measure, Indicate and control the temperature of a specific applications, like Transformers oil , Generators, Bearing temperature monitoring etc…
Dial type thermometer 4007h
Dial Type Thermometer 4007H
Dial type thermometers are liquid filled in the closed system and DTT consists of Bulb assembly, capillary and Expansion bel-lows. If the temperature changes, the internal pressure of the thermometer changes as well. The pressure is transferred through capillary to a pointer shaft and thus the temperature values are indicated on scale.
OTI and BTD works without external power for its operation and indicates corresponding oil temperature on front panel.
WTI construction is also similar to OTI, in addition to that CT are provided to measure the winding temperature plus winding temperature above hot level, i.e the hot spot temperature.
WTI are provided with gradient adjustment through a shunt for CT secondary in-put (1A to 5A)
Features
- 4.5 inch/115 mm Segmental Dial face for clear temperature indication.
- 4 no’s of adjustable switches for control and alarm’s.
- Accuracy Range with in ±1.5% of full scale
- IP-55 Protection
- 60º Angular sweep with 2℃ each graduation
- Panel Mounting option provided
Hybrid Instrument
- Hybrid Instruments are high performance temperature monitoring instrument with built in PT-100 sensor (RTD) & Current Converter Unit and external Remote Indicator
- Instrument casings are Aluminum die casted and PU coated for weather proof, All in-side and outside components are Brass and SS304.
Technical Specification
SL NO | PARAMETERS | DESCRIPTION | UNIT |
---|---|---|---|
01 | Temperature Range | 0 to 150 (-10 to150 Optional) | ºC |
02 | Angular Sweep | 60 | ºC |
03 | Accuracy class | ± 1.5% of full scale | ºC |
04 | Dial Graduations | 2 | ºC |
05 | Max. No of Switch | 4 | No’s |
06 | Switch Rating | 15A @ 250V AC , 0.5A @ 220V DC | |
07 | Switch Differential | S1 & S2 : 5-10 | |
08 | Switch | NO type | |
09 | Switch Accuracy | ± 4 | ºC |
10 | Max. Capillary Length | Upto 15 | Meters |
11 | Degree of protection | IP-55 | |
12 | High voltage test | 2.5kv AC, 50Hz/60Hz for 1 minute, all terminal to ground |
How To Order?
1.CURRENT CONVERTER UNIT
a | Power Supply | 90-275V AC/DC |
b | Input | PT 100 RTD ( 3 wire Simplex) |
c | CT Signal in case of WTI | 0-5A AC |
d | Signal Output | Upto 2 sets of 4-20mA DC ( 600 Ohm re- sistance burden including cable resistance ) |
e | Overall Dimension | 100(L) X 75 (W) X 112(D) MM with Din rail Mount |
f | Ambient Operating Temper- ature | 0- 50 ° C And 10 – 80 RH |
g | Storing Temperature | -10°-60° and 10-90 RH |
h | Degree of Protection of En- closure | IP 40 |
2.REMOTE INDICATOR UNIT
a | Power Supply | 90-275V AC/DC |
b | Display | 4 Digits , 0.56 Inch , 7 Segment Red colour Display |
c | Resolution | 0.1 ° C |
d | Input | 4-20mA Signals from CCU |
e | Signal Output | Upto 4 sets of 4-20mA DC |
f | SCADA Communication | RS485 RTU Protocol |
g | Overall Dimension | 96(L)X 96(W)X110(D) MM with Panel mount Option ( Panel cut out dimension – 92 Sq mm |
h | Ambient Operating Temper- ature | 0- 50 ° C And 10 – 80 RH |
i | Storing Temperature | -10°-60° and 10-90RH |
j | Degree of Protection of En- closure | IP 20 |